Combustion behaviour of polyurethane flexible foams under Cone Calorimetry test conditions

Vanspeybroeck, R. ; Van Hees, P. LU and Vandevelde, P. (1993) In Fire and Materials 17(4). p.155-166
Abstract

The first part of this study focuses on the effect of cone calorimeter test variables on polyurethane flexible foam properties such as ignitability, heat release rate, effective heat of combustion and mass loss. Three of the main commercial foam types were used, i.e. conventional slabstock foams, high‐resilience slabstock foams and all‐MDI (methylene diphenyldiisocyanate) moulded foams. A decrease in heat flux (down to 40%) with increasing distance from the conical heater was measured. As a consequence, results were found to depend to a large extent on the thickness and the melting behaviour of the foam samples. To achieve a sufficiently constant and uniform heat flux exposure, sample thickness had to be limited to 25 mm. In addition,... (More)

The first part of this study focuses on the effect of cone calorimeter test variables on polyurethane flexible foam properties such as ignitability, heat release rate, effective heat of combustion and mass loss. Three of the main commercial foam types were used, i.e. conventional slabstock foams, high‐resilience slabstock foams and all‐MDI (methylene diphenyldiisocyanate) moulded foams. A decrease in heat flux (down to 40%) with increasing distance from the conical heater was measured. As a consequence, results were found to depend to a large extent on the thickness and the melting behaviour of the foam samples. To achieve a sufficiently constant and uniform heat flux exposure, sample thickness had to be limited to 25 mm. In addition, repeatability was found to be good under various conditions, with percentage standard deviations for effective heat of combustion, peak rate of heat release and mass loss below 10%. Levels of radiant flux above 25 kW m−2 were found to be very severe to test flexible polyurethane foams. Under such conditions, foams that show large differences in combustion performance in small‐scale flammability tests performed almost identically in the cone calorimeter. In the second part of this study the effects of foam variables, such as foam type, density and melamine content, are defined. These effects were clearly pronounced at radiant flux levels of 15–25 kWm−2. Density was found to be the key variable in controlling ignition resistance. In addition, high‐resilience slabstock foams and all‐MDI moulded foams performed better than conventional slabstock foams of the same density. Melamine addition resulted in a delay of ignition for all three foam types and an incomplete combustion, decreased heat release and effective heat of combustion in HR‐slabstock and all MDI moulded foams. However, melamine is not effective as a heat sink in conventional slabstock foams. The different performance of the foam types under study can be explained by a different melting behaviour.

(Less)
Please use this url to cite or link to this publication:
author
; and
publishing date
type
Contribution to journal
publication status
published
in
Fire and Materials
volume
17
issue
4
pages
12 pages
publisher
John Wiley & Sons Inc.
external identifiers
  • scopus:0027632154
ISSN
0308-0501
DOI
10.1002/fam.810170403
language
English
LU publication?
no
id
cebca313-bbe1-4a4b-8803-94b3c1c973bc
date added to LUP
2016-11-05 14:10:08
date last changed
2021-09-19 05:03:39
@article{cebca313-bbe1-4a4b-8803-94b3c1c973bc,
  abstract     = {{<p>The first part of this study focuses on the effect of cone calorimeter test variables on polyurethane flexible foam properties such as ignitability, heat release rate, effective heat of combustion and mass loss. Three of the main commercial foam types were used, i.e. conventional slabstock foams, high‐resilience slabstock foams and all‐MDI (methylene diphenyldiisocyanate) moulded foams. A decrease in heat flux (down to 40%) with increasing distance from the conical heater was measured. As a consequence, results were found to depend to a large extent on the thickness and the melting behaviour of the foam samples. To achieve a sufficiently constant and uniform heat flux exposure, sample thickness had to be limited to 25 mm. In addition, repeatability was found to be good under various conditions, with percentage standard deviations for effective heat of combustion, peak rate of heat release and mass loss below 10%. Levels of radiant flux above 25 kW m<sup>−2</sup> were found to be very severe to test flexible polyurethane foams. Under such conditions, foams that show large differences in combustion performance in small‐scale flammability tests performed almost identically in the cone calorimeter. In the second part of this study the effects of foam variables, such as foam type, density and melamine content, are defined. These effects were clearly pronounced at radiant flux levels of 15–25 kWm<sup>−2</sup>. Density was found to be the key variable in controlling ignition resistance. In addition, high‐resilience slabstock foams and all‐MDI moulded foams performed better than conventional slabstock foams of the same density. Melamine addition resulted in a delay of ignition for all three foam types and an incomplete combustion, decreased heat release and effective heat of combustion in HR‐slabstock and all MDI moulded foams. However, melamine is not effective as a heat sink in conventional slabstock foams. The different performance of the foam types under study can be explained by a different melting behaviour.</p>}},
  author       = {{Vanspeybroeck, R. and Van Hees, P. and Vandevelde, P.}},
  issn         = {{0308-0501}},
  language     = {{eng}},
  number       = {{4}},
  pages        = {{155--166}},
  publisher    = {{John Wiley & Sons Inc.}},
  series       = {{Fire and Materials}},
  title        = {{Combustion behaviour of polyurethane flexible foams under Cone Calorimetry test conditions}},
  url          = {{http://dx.doi.org/10.1002/fam.810170403}},
  doi          = {{10.1002/fam.810170403}},
  volume       = {{17}},
  year         = {{1993}},
}