Brandteknisk riskvärdering av Tyrs Hov

Clarin, Christoffer ; Åkesson, Olof M. and Olsson, Pontus (2012) In BTR VBR054 20121
Division of Fire Safety Engineering
Division of Risk Management and Societal Safety
Abstract
The following report is an evaluation of the fire safety for Tyrs Hov sports center in Tyringe with emphasis and focus on personal safety in and egress out of the building. The report was produced as part of studying the course Fire Safety Evaluation at the Department of Fire Safety Engineering and Systems Safety at Lund University.

Tyrs Hov holds a variety of sporting activities scattered throughout a building holding several floors. Assessment is by means of qualitative and quantitative techniques, where a rough analysis of the relevant fire hazards within the facility is made. From there, a number of fire scenarios are chosen for further analysis, which together cover relevant fire hazards
Analysis is done using statistical data,... (More)
The following report is an evaluation of the fire safety for Tyrs Hov sports center in Tyringe with emphasis and focus on personal safety in and egress out of the building. The report was produced as part of studying the course Fire Safety Evaluation at the Department of Fire Safety Engineering and Systems Safety at Lund University.

Tyrs Hov holds a variety of sporting activities scattered throughout a building holding several floors. Assessment is by means of qualitative and quantitative techniques, where a rough analysis of the relevant fire hazards within the facility is made. From there, a number of fire scenarios are chosen for further analysis, which together cover relevant fire hazards
Analysis is done using statistical data, estimates and simulation programs supplemented by hand calculations. The simulation programs used are FDS 5, CFAST 6 and Simulex. Where existing safety systems appear to fail, new suggested measures are implemented to the model, which is then re-analyzed to become subsequently established.

The results of the evaluation indicate that the personal safety due to a fire scenario at Tyrs Hov can ́t be regarded as sufficient. If Tyrs Hov would carry through the suggested measures, e.g. the construction of a new fire exit for the bowling alley, the fire safety regarding egress and personal safety in the enclosure chosen for analysis could be considered as adequate. (Less)
Please use this url to cite or link to this publication:
author
Clarin, Christoffer ; Åkesson, Olof M. and Olsson, Pontus
supervisor
organization
alternative title
Fire safety evaluation of Tyrs Hov
course
VBR054 20121
year
type
L3 - Miscellaneous, Projetcs etc.
subject
keywords
brandscenario, brandteknisk riskvärdering, CFD, effektutveckling, FDS, kritiska förhållanden, personsäkerhet, Tyrs Hov, grovanalys, Simulex, känslighetsanalys, utrymning, utrymningstid.
publication/series
BTR
report number
9413
language
Swedish
id
3052026
date added to LUP
2012-09-12 13:00:37
date last changed
2014-03-10 10:40:43
@misc{3052026,
  abstract     = {{The following report is an evaluation of the fire safety for Tyrs Hov sports center in Tyringe with emphasis and focus on personal safety in and egress out of the building. The report was produced as part of studying the course Fire Safety Evaluation at the Department of Fire Safety Engineering and Systems Safety at Lund University.

Tyrs Hov holds a variety of sporting activities scattered throughout a building holding several floors. Assessment is by means of qualitative and quantitative techniques, where a rough analysis of the relevant fire hazards within the facility is made. From there, a number of fire scenarios are chosen for further analysis, which together cover relevant fire hazards
Analysis is done using statistical data, estimates and simulation programs supplemented by hand calculations. The simulation programs used are FDS 5, CFAST 6 and Simulex. Where existing safety systems appear to fail, new suggested measures are implemented to the model, which is then re-analyzed to become subsequently established.

The results of the evaluation indicate that the personal safety due to a fire scenario at Tyrs Hov can ́t be regarded as sufficient. If Tyrs Hov would carry through the suggested measures, e.g. the construction of a new fire exit for the bowling alley, the fire safety regarding egress and personal safety in the enclosure chosen for analysis could be considered as adequate.}},