Brandteknisk Riskvärdering av China Teatern
(2016) VBR054 20161Division of Fire Safety Engineering
- Abstract
- The purpose of this report is to evaluate the fire safety for the visitors at China Teatern. The theatre is situated in central Stockholm, Sweden, and houses up to 1249 visitors. This report does not consider damage done to property or to the surrounding environment.
After a visit at the theatre in February 2016, various data was gathered and analyzed. A dozen fire scenarios were identified and evaluated. The two most hazardous scenarios were picked out for further analysis. Simulations in FDS, Pathfinder and @Risk were made in order to compare the total evacuation time with the time until critical conditions occurred. In the cases where the time until critical conditions exceeded the time for total evacuation, suggestions to improve the... (More) - The purpose of this report is to evaluate the fire safety for the visitors at China Teatern. The theatre is situated in central Stockholm, Sweden, and houses up to 1249 visitors. This report does not consider damage done to property or to the surrounding environment.
After a visit at the theatre in February 2016, various data was gathered and analyzed. A dozen fire scenarios were identified and evaluated. The two most hazardous scenarios were picked out for further analysis. Simulations in FDS, Pathfinder and @Risk were made in order to compare the total evacuation time with the time until critical conditions occurred. In the cases where the time until critical conditions exceeded the time for total evacuation, suggestions to improve the fire safety were provided in order to ensure the safety of the visitors. (Less)
Please use this url to cite or link to this publication:
http://lup.lub.lu.se/student-papers/record/8876364
- author
- Troell, Simon LU ; Selmani, Dastid ; Rydberg, Love and Rasmusson, Kevin
- supervisor
- organization
- course
- VBR054 20161
- year
- 2016
- type
- L3 - Miscellaneous, Projetcs etc.
- subject
- keywords
- China Teatern, Risk evaluation, egress, FDS, Pathfinder, @Risk
- report number
- 9491
- language
- Swedish
- id
- 8876364
- date added to LUP
- 2016-06-21 16:25:55
- date last changed
- 2016-06-21 16:25:55
@misc{8876364, abstract = {{The purpose of this report is to evaluate the fire safety for the visitors at China Teatern. The theatre is situated in central Stockholm, Sweden, and houses up to 1249 visitors. This report does not consider damage done to property or to the surrounding environment. After a visit at the theatre in February 2016, various data was gathered and analyzed. A dozen fire scenarios were identified and evaluated. The two most hazardous scenarios were picked out for further analysis. Simulations in FDS, Pathfinder and @Risk were made in order to compare the total evacuation time with the time until critical conditions occurred. In the cases where the time until critical conditions exceeded the time for total evacuation, suggestions to improve the fire safety were provided in order to ensure the safety of the visitors.}}, author = {{Troell, Simon and Selmani, Dastid and Rydberg, Love and Rasmusson, Kevin}}, language = {{swe}}, note = {{Student Paper}}, title = {{Brandteknisk Riskvärdering av China Teatern}}, year = {{2016}}, }