Pyrotekniskt genererade aerosoler - experimentella studier med avseende på funktion och risker rörande människa och teknik

Ekström, Jonas and Nilsson, Björn (2009) In LUTVDG/TVBB--5263--SE
Division of Fire Safety Engineering
Fire Protection Engineering 3,5 years
Division of Risk Management and Societal Safety
Abstract
This report is a study on the effects pyrotechnically generated aerosols, PGA, has on electrical components and our health. Experiments were conducted in small and full scale at Lunds tekniska högskola and the Swedish rescue service’s school at Revinge. The experiments were
conducted using only one type of PGA with exception for the full scale experiments in wich two types were used. The experiments conducted were: studies on what effect a sedimented aerosol had on low voltage circuits? Does an aerosol lower energy needed for an electric discharge between to points in a high voltage system? What is the effect on sight conditions in
an enclosure filled with an aerosol? Does the PGA fulfil the requirements in various regulations regarding... (More)
This report is a study on the effects pyrotechnically generated aerosols, PGA, has on electrical components and our health. Experiments were conducted in small and full scale at Lunds tekniska högskola and the Swedish rescue service’s school at Revinge. The experiments were
conducted using only one type of PGA with exception for the full scale experiments in wich two types were used. The experiments conducted were: studies on what effect a sedimented aerosol had on low voltage circuits? Does an aerosol lower energy needed for an electric discharge between to points in a high voltage system? What is the effect on sight conditions in
an enclosure filled with an aerosol? Does the PGA fulfil the requirements in various regulations regarding sound levels and discharge times? Is the PGA toxic? What is the particle size distribution? Can a PGA extinguish fires in cabinets placed in a PGA protected
enclosure? The answer to all these questions was very satisfying and the results showed that the PGA is a very good extinguishing agent and the effect on electrical components was minimal. One concern is the effect on humans, the levels of ammonia and carbon monoxide generated by
the PGA was very high, leading to the conclusion that a PGA system should not be installed in enclosures normally occupied by persons. (Less)
Please use this url to cite or link to this publication:
author
Ekström, Jonas and Nilsson, Björn
supervisor
organization
year
type
M2 - Bachelor Degree
subject
keywords
Pyrotekniskt genererade aerosoler, gasformiga släckmedel, PGA, hälsorisker
publication/series
LUTVDG/TVBB--5263--SE
report number
5263
ISSN
1402-3504
language
Swedish
id
1767679
date added to LUP
2011-01-25 09:24:05
date last changed
2014-03-10 10:40:36
@misc{1767679,
  abstract     = {{This report is a study on the effects pyrotechnically generated aerosols, PGA, has on electrical components and our health. Experiments were conducted in small and full scale at Lunds tekniska högskola and the Swedish rescue service’s school at Revinge. The experiments were
conducted using only one type of PGA with exception for the full scale experiments in wich two types were used. The experiments conducted were: studies on what effect a sedimented aerosol had on low voltage circuits? Does an aerosol lower energy needed for an electric discharge between to points in a high voltage system? What is the effect on sight conditions in
an enclosure filled with an aerosol? Does the PGA fulfil the requirements in various regulations regarding sound levels and discharge times? Is the PGA toxic? What is the particle size distribution? Can a PGA extinguish fires in cabinets placed in a PGA protected
enclosure? The answer to all these questions was very satisfying and the results showed that the PGA is a very good extinguishing agent and the effect on electrical components was minimal. One concern is the effect on humans, the levels of ammonia and carbon monoxide generated by
the PGA was very high, leading to the conclusion that a PGA system should not be installed in enclosures normally occupied by persons.}},
  author       = {{Ekström, Jonas and Nilsson, Björn}},
  issn         = {{1402-3504}},
  language     = {{swe}},
  note         = {{Student Paper}},
  series       = {{LUTVDG/TVBB--5263--SE}},
  title        = {{Pyrotekniskt genererade aerosoler - experimentella studier med avseende på funktion och risker rörande människa och teknik}},
  year         = {{2009}},
}