Brandteknisk riskvärdering av Galleria Domino

Degerman, Helene ; Nero, Carin ; Nilsson, Henrik and Szymanski, Johan (2007)
Division of Fire Safety Engineering
Fire Protection Engineering 3,5 years
Division of Risk Management and Societal Safety
Abstract
This report is a fire safety evaluation of Norrköping shopping mall Domino and the report focus on evacuation and human safety. During a visit in Norrköping three different scenarios were found based on an analysis of consequences. The scenarios have been evaluated and
simulated in for example CFast, Simulex and DetactT2. Different parameters as for example smoke filling and temperature rise have been analyzed in the three scenarios. Suggestions for improvement of Domino fire safety are for example education of employees, smoke detectors in all spaces, keep fire exits clean from combustible materials and sprinkler
placement according to concrete beams in the ceiling should be assessed. The main conclusion of this report is that... (More)
This report is a fire safety evaluation of Norrköping shopping mall Domino and the report focus on evacuation and human safety. During a visit in Norrköping three different scenarios were found based on an analysis of consequences. The scenarios have been evaluated and
simulated in for example CFast, Simulex and DetactT2. Different parameters as for example smoke filling and temperature rise have been analyzed in the three scenarios. Suggestions for improvement of Domino fire safety are for example education of employees, smoke detectors in all spaces, keep fire exits clean from combustible materials and sprinkler
placement according to concrete beams in the ceiling should be assessed. The main conclusion of this report is that evacuation can be completed with satisfaction even though there are critical conditions in some compartments. If the suggested improvements are followed the time of total evacuation of Domino can be shortened by about two minutes. (Less)
Please use this url to cite or link to this publication:
author
Degerman, Helene ; Nero, Carin ; Nilsson, Henrik and Szymanski, Johan
supervisor
organization
year
type
L3 - Miscellaneous, Projetcs etc.
subject
keywords
CFast, Simulex, utrymning, kritiska förhållanden, brandgas, galleria, DetactT2, brandteknisk riskvärdering.
report number
9325
language
Swedish
id
1776161
date added to LUP
2011-02-02 09:09:18
date last changed
2014-03-10 10:40:37
@misc{1776161,
  abstract     = {{This report is a fire safety evaluation of Norrköping shopping mall Domino and the report focus on evacuation and human safety. During a visit in Norrköping three different scenarios were found based on an analysis of consequences. The scenarios have been evaluated and
simulated in for example CFast, Simulex and DetactT2. Different parameters as for example smoke filling and temperature rise have been analyzed in the three scenarios. Suggestions for improvement of Domino fire safety are for example education of employees, smoke detectors in all spaces, keep fire exits clean from combustible materials and sprinkler
placement according to concrete beams in the ceiling should be assessed. The main conclusion of this report is that evacuation can be completed with satisfaction even though there are critical conditions in some compartments. If the suggested improvements are followed the time of total evacuation of Domino can be shortened by about two minutes.}},
  author       = {{Degerman, Helene and Nero, Carin and Nilsson, Henrik and Szymanski, Johan}},
  language     = {{swe}},
  note         = {{Student Paper}},
  title        = {{Brandteknisk riskvärdering av Galleria Domino}},
  year         = {{2007}},
}