Brandteknisk Riskvärdering av COOP Forum Nyköping

Falkman, Fredrik ; Magnusson, Johan ; Nilsson, Gustav and Pettersson, Carl (2011) VBR054 20111
Division of Fire Safety Engineering
Division of Risk Management and Societal Safety
Abstract
This report is an analysis of the evacuation capabilities of COOP Forum Nyköping. COOP Forum is a 6800 square meter supermarket built in 1970. The building is fitted with a sprinkler system, but lacks an automatic detection system in the sales part of the building. Two likely scenarios were identified and then simulated in FDS 5. In case of a fire in the personnel department, the smoke quickly filled the second floor and blocked off the only available emergency exit. It is therefore recommended that a smoke-proof door is installed in the staff dining room, which shuts automatically in the event of a fire. In the sales department, critical conditions were not attained before all customers had evacuated safely. To increase the safety margins... (More)
This report is an analysis of the evacuation capabilities of COOP Forum Nyköping. COOP Forum is a 6800 square meter supermarket built in 1970. The building is fitted with a sprinkler system, but lacks an automatic detection system in the sales part of the building. Two likely scenarios were identified and then simulated in FDS 5. In case of a fire in the personnel department, the smoke quickly filled the second floor and blocked off the only available emergency exit. It is therefore recommended that a smoke-proof door is installed in the staff dining room, which shuts automatically in the event of a fire. In the sales department, critical conditions were not attained before all customers had evacuated safely. To increase the safety margins it is, however, recommended that a smoke detector system is installed in the sales area. (Less)
Please use this url to cite or link to this publication:
author
Falkman, Fredrik ; Magnusson, Johan ; Nilsson, Gustav and Pettersson, Carl
supervisor
organization
course
VBR054 20111
year
type
L3 - Miscellaneous, Projetcs etc.
subject
keywords
@RISK, brandscenarier, brandteknisk riskvärdering, COOP Forum, Detact QS, effektutveckling, FDS 5, kritiska förhållanden, personsäkerhet, Simulex, utrymning.
report number
9389
language
Swedish
id
2063154
date added to LUP
2011-08-18 13:41:31
date last changed
2014-03-10 10:40:39
@misc{2063154,
  abstract     = {{This report is an analysis of the evacuation capabilities of COOP Forum Nyköping. COOP Forum is a 6800 square meter supermarket built in 1970. The building is fitted with a sprinkler system, but lacks an automatic detection system in the sales part of the building. Two likely scenarios were identified and then simulated in FDS 5. In case of a fire in the personnel department, the smoke quickly filled the second floor and blocked off the only available emergency exit. It is therefore recommended that a smoke-proof door is installed in the staff dining room, which shuts automatically in the event of a fire. In the sales department, critical conditions were not attained before all customers had evacuated safely. To increase the safety margins it is, however, recommended that a smoke detector system is installed in the sales area.}},
  author       = {{Falkman, Fredrik and Magnusson, Johan and Nilsson, Gustav and Pettersson, Carl}},
  language     = {{swe}},
  note         = {{Student Paper}},
  title        = {{Brandteknisk Riskvärdering av COOP Forum Nyköping}},
  year         = {{2011}},
}