Heating and Cooling of the Supply air in Fan-assisted Natural Ventilation

Nordquist, Birgitta LU (2009) AIVC 2009, “Trends in High performance Buildings and the role of Ventilation
Abstract
In schools the temperature of the indoor air is one of the most important factors in terms of the indoor climate. The resulting indoor air temperature is depending on many factors; the temperature of the supply air being one of the more significant one. One fan-assisted natural ventilation system includes a supply air system where the outdoor air should be passively heated respectively cooled when passing components in the ground before it is supplied to the classrooms. The objective is to examine the ability of the supply system to transfer heat to/from the outdoor air. This has been studied by measurements of the air temperature at several measurement points in a real school building. The results show that the supply air system has an... (More)
In schools the temperature of the indoor air is one of the most important factors in terms of the indoor climate. The resulting indoor air temperature is depending on many factors; the temperature of the supply air being one of the more significant one. One fan-assisted natural ventilation system includes a supply air system where the outdoor air should be passively heated respectively cooled when passing components in the ground before it is supplied to the classrooms. The objective is to examine the ability of the supply system to transfer heat to/from the outdoor air. This has been studied by measurements of the air temperature at several measurement points in a real school building. The results show that the supply air system has an ability to heat respectively cool the outdoor air. The heat transfer results in a supply air temperature within a rather narrow interval, regardless of outdoor air temperature. The consequence of cooling hot humid air leads to high relative humidity which means that a risk for mould growth may occur which should be avoided. This must be observed and handled if designing this form of system. (Less)
Please use this url to cite or link to this publication:
author
organization
publishing date
type
Chapter in Book/Report/Conference proceeding
publication status
published
subject
keywords
Supply air, temperature, passive heating, natural ventilation
host publication
AIVC, Proceedings of the 30th AIVC Conference
pages
6 pages
conference name
AIVC 2009, “Trends in High performance Buildings and the role of Ventilation
conference location
Berlin, Germany
conference dates
2009-10-01 - 2009-10-02
language
English
LU publication?
yes
id
87f505b5-b600-47e4-97a1-25f000fd6f36 (old id 3173344)
date added to LUP
2016-04-04 13:48:19
date last changed
2018-11-21 21:16:24
@inproceedings{87f505b5-b600-47e4-97a1-25f000fd6f36,
  abstract     = {{In schools the temperature of the indoor air is one of the most important factors in terms of the indoor climate. The resulting indoor air temperature is depending on many factors; the temperature of the supply air being one of the more significant one. One fan-assisted natural ventilation system includes a supply air system where the outdoor air should be passively heated respectively cooled when passing components in the ground before it is supplied to the classrooms. The objective is to examine the ability of the supply system to transfer heat to/from the outdoor air. This has been studied by measurements of the air temperature at several measurement points in a real school building. The results show that the supply air system has an ability to heat respectively cool the outdoor air. The heat transfer results in a supply air temperature within a rather narrow interval, regardless of outdoor air temperature. The consequence of cooling hot humid air leads to high relative humidity which means that a risk for mould growth may occur which should be avoided. This must be observed and handled if designing this form of system.}},
  author       = {{Nordquist, Birgitta}},
  booktitle    = {{AIVC, Proceedings of the 30th AIVC Conference}},
  keywords     = {{Supply air; temperature; passive heating; natural ventilation}},
  language     = {{eng}},
  title        = {{Heating and Cooling of the Supply air in Fan-assisted Natural Ventilation}},
  year         = {{2009}},
}