The effect of accelerated ageing of building wires

Emanuelsson, Viktor ; Simonson, Margaret LU and Gevert, Thomas (2007) In Fire and Materials 31(5). p.311-326
Abstract

The fire performance of two electric cables (building wires) designed for indoor use has been tested, both as new products and after accelerated thermooxidative ageing. The cables were aged for a maximum time of 16.5 weeks at 80°C. The cables are commercially available, and were constructed using a PVC material in one case and a non-halogenated polyolefin-based material, called Casico, in the other. The effects of ageing on the fire performance of the cables, and the chemical changes that have caused the observed fire behaviour, have been investigated and are discussed. Special attention is paid to the behaviour of the plasticizers that are used in the PVC cable, and how the fire behaviour is affected by the loss of plasticizers from... (More)

The fire performance of two electric cables (building wires) designed for indoor use has been tested, both as new products and after accelerated thermooxidative ageing. The cables were aged for a maximum time of 16.5 weeks at 80°C. The cables are commercially available, and were constructed using a PVC material in one case and a non-halogenated polyolefin-based material, called Casico, in the other. The effects of ageing on the fire performance of the cables, and the chemical changes that have caused the observed fire behaviour, have been investigated and are discussed. Special attention is paid to the behaviour of the plasticizers that are used in the PVC cable, and how the fire behaviour is affected by the loss of plasticizers from the cable and by the migration of plasticizers between the parts of the cable (insulation, bedding and sheathing).

(Less)
Please use this url to cite or link to this publication:
author
; and
publishing date
type
Contribution to journal
publication status
published
subject
keywords
Ageing, Casico, Cone calorimeter, Electric cables, Fire, PVC
in
Fire and Materials
volume
31
issue
5
pages
16 pages
publisher
John Wiley & Sons Inc.
external identifiers
  • scopus:34547574450
ISSN
0308-0501
DOI
10.1002/fam.944
language
English
LU publication?
no
additional info
Copyright: Copyright 2008 Elsevier B.V., All rights reserved.
id
90ecadd1-0352-41d4-bf82-f5a4fe79b164
date added to LUP
2021-09-29 14:26:41
date last changed
2022-02-09 08:58:19
@article{90ecadd1-0352-41d4-bf82-f5a4fe79b164,
  abstract     = {{<p>The fire performance of two electric cables (building wires) designed for indoor use has been tested, both as new products and after accelerated thermooxidative ageing. The cables were aged for a maximum time of 16.5 weeks at 80°C. The cables are commercially available, and were constructed using a PVC material in one case and a non-halogenated polyolefin-based material, called Casico, in the other. The effects of ageing on the fire performance of the cables, and the chemical changes that have caused the observed fire behaviour, have been investigated and are discussed. Special attention is paid to the behaviour of the plasticizers that are used in the PVC cable, and how the fire behaviour is affected by the loss of plasticizers from the cable and by the migration of plasticizers between the parts of the cable (insulation, bedding and sheathing).</p>}},
  author       = {{Emanuelsson, Viktor and Simonson, Margaret and Gevert, Thomas}},
  issn         = {{0308-0501}},
  keywords     = {{Ageing; Casico; Cone calorimeter; Electric cables; Fire; PVC}},
  language     = {{eng}},
  number       = {{5}},
  pages        = {{311--326}},
  publisher    = {{John Wiley & Sons Inc.}},
  series       = {{Fire and Materials}},
  title        = {{The effect of accelerated ageing of building wires}},
  url          = {{http://dx.doi.org/10.1002/fam.944}},
  doi          = {{10.1002/fam.944}},
  volume       = {{31}},
  year         = {{2007}},
}