Galvanic corrosion properties of steel in water saturated concrete

Ahlstrom, J. ; Tidblad, J. ; Sandberg, B. and Wadsö, Lars LU (2015) In Materials and Corrosion 66(1). p.67-75
Abstract
Aluminum-based sacrificial anodes were installed to reinforced concrete to stop ongoing corrosion in cooling water tunnels in a Swedish nuclear power plant. The steel rebars were also unintentionally connected to stainless steel water pumps. Therefore, the consumption rate of the sacrificial anodes was higher than predicted. An experimental and a field study were performed to assess if the steel rebar suffer from galvanic corrosion and if the stainless steel pumps are responsible alone for the high consumption rate. It was found from the experimental study that there is an increased risk of galvanic corrosion for steel rebar when the corrosion potential is raised to -200mV (SCE) for samples with 1% Cl- by mass of cement and -500mV (SCE)... (More)
Aluminum-based sacrificial anodes were installed to reinforced concrete to stop ongoing corrosion in cooling water tunnels in a Swedish nuclear power plant. The steel rebars were also unintentionally connected to stainless steel water pumps. Therefore, the consumption rate of the sacrificial anodes was higher than predicted. An experimental and a field study were performed to assess if the steel rebar suffer from galvanic corrosion and if the stainless steel pumps are responsible alone for the high consumption rate. It was found from the experimental study that there is an increased risk of galvanic corrosion for steel rebar when the corrosion potential is raised to -200mV (SCE) for samples with 1% Cl- by mass of cement and -500mV (SCE) for samples with 2% Cl- by mass of cement. The experimental results were compared with the corrosion potential measured in the cooling water tunnel where sacrificial anodes were in use and not mounted at all. The cooling water tunnel without sacrificial anodes had generally more anodic corrosion potentials compared to the tunnel with anodes. The tunnel with anodes had also more anodic potentials closer to the stainless steel pumps than further away which means that the rebar is affected by the stainless steel pumps. However, the measured corrosion potentials in the tunnels were not as anodic as the potentials needed for high galvanic current measured in the experimental study. (Less)
Please use this url to cite or link to this publication:
author
; ; and
organization
publishing date
type
Contribution to journal
publication status
published
subject
in
Materials and Corrosion
volume
66
issue
1
pages
67 - 75
publisher
John Wiley & Sons Inc.
external identifiers
  • wos:000347711300009
  • scopus:84920848908
ISSN
1521-4176
DOI
10.1002/maco.201307141
language
English
LU publication?
yes
id
dc11ef4c-5b9e-4fb1-bcc7-c21b21a29188 (old id 5070044)
date added to LUP
2016-04-01 10:27:34
date last changed
2022-01-25 23:26:12
@article{dc11ef4c-5b9e-4fb1-bcc7-c21b21a29188,
  abstract     = {{Aluminum-based sacrificial anodes were installed to reinforced concrete to stop ongoing corrosion in cooling water tunnels in a Swedish nuclear power plant. The steel rebars were also unintentionally connected to stainless steel water pumps. Therefore, the consumption rate of the sacrificial anodes was higher than predicted. An experimental and a field study were performed to assess if the steel rebar suffer from galvanic corrosion and if the stainless steel pumps are responsible alone for the high consumption rate. It was found from the experimental study that there is an increased risk of galvanic corrosion for steel rebar when the corrosion potential is raised to -200mV (SCE) for samples with 1% Cl- by mass of cement and -500mV (SCE) for samples with 2% Cl- by mass of cement. The experimental results were compared with the corrosion potential measured in the cooling water tunnel where sacrificial anodes were in use and not mounted at all. The cooling water tunnel without sacrificial anodes had generally more anodic corrosion potentials compared to the tunnel with anodes. The tunnel with anodes had also more anodic potentials closer to the stainless steel pumps than further away which means that the rebar is affected by the stainless steel pumps. However, the measured corrosion potentials in the tunnels were not as anodic as the potentials needed for high galvanic current measured in the experimental study.}},
  author       = {{Ahlstrom, J. and Tidblad, J. and Sandberg, B. and Wadsö, Lars}},
  issn         = {{1521-4176}},
  language     = {{eng}},
  number       = {{1}},
  pages        = {{67--75}},
  publisher    = {{John Wiley & Sons Inc.}},
  series       = {{Materials and Corrosion}},
  title        = {{Galvanic corrosion properties of steel in water saturated concrete}},
  url          = {{http://dx.doi.org/10.1002/maco.201307141}},
  doi          = {{10.1002/maco.201307141}},
  volume       = {{66}},
  year         = {{2015}},
}