Controlled island operation of part of the 50-kV grid in Southern Sweden
(2009) IEEE Power Tech 2009 p.1-6- Abstract
- Abstract in Undetermined
This paper is based on measurements obtained during a test of controlled islanding of part of the 50-kV grid in Southern Sweden. The purpose of the test was to verify operation of generator controls during islanding. The variations in voltage magnitude and frequency are shown as well as flicker severity and very-short variations. A number of performance indices have been calculated and compared with limits. Voltage magnitude and frequency have been studied in some detail around the disconnection and reconnection instants. The frequency varies much more during the island operation than during grid-connected operation. Voltage magnitude variations and flicker remain within their normal range. However the... (More) - Abstract in Undetermined
This paper is based on measurements obtained during a test of controlled islanding of part of the 50-kV grid in Southern Sweden. The purpose of the test was to verify operation of generator controls during islanding. The variations in voltage magnitude and frequency are shown as well as flicker severity and very-short variations. A number of performance indices have been calculated and compared with limits. Voltage magnitude and frequency have been studied in some detail around the disconnection and reconnection instants. The frequency varies much more during the island operation than during grid-connected operation. Voltage magnitude variations and flicker remain within their normal range. However the variations in the time range between 3 seconds and 10 minute appear to be higher than normal. (Less)
Please use this url to cite or link to this publication:
https://lup.lub.lu.se/record/2535814
- author
- Bollen, Math and Samuelsson, Olof LU
- organization
- publishing date
- 2009
- type
- Chapter in Book/Report/Conference proceeding
- publication status
- published
- subject
- host publication
- PowerTech, 2009 IEEE Bucharest
- pages
- 1 - 6
- conference name
- IEEE Power Tech 2009
- conference location
- Bucharest, Romania
- conference dates
- 2009-06-28 - 2009-07-02
- external identifiers
-
- scopus:74949127911
- ISBN
- 978-1-4244-2234-0
- DOI
- 10.1109/PTC.2009.5282130
- language
- English
- LU publication?
- yes
- id
- 7b27ac62-7152-4171-a4bd-68c2e3add57e (old id 2535814)
- date added to LUP
- 2016-04-04 14:34:39
- date last changed
- 2022-01-30 02:17:09
@inproceedings{7b27ac62-7152-4171-a4bd-68c2e3add57e, abstract = {{Abstract in Undetermined<br/>This paper is based on measurements obtained during a test of controlled islanding of part of the 50-kV grid in Southern Sweden. The purpose of the test was to verify operation of generator controls during islanding. The variations in voltage magnitude and frequency are shown as well as flicker severity and very-short variations. A number of performance indices have been calculated and compared with limits. Voltage magnitude and frequency have been studied in some detail around the disconnection and reconnection instants. The frequency varies much more during the island operation than during grid-connected operation. Voltage magnitude variations and flicker remain within their normal range. However the variations in the time range between 3 seconds and 10 minute appear to be higher than normal.}}, author = {{Bollen, Math and Samuelsson, Olof}}, booktitle = {{PowerTech, 2009 IEEE Bucharest}}, isbn = {{978-1-4244-2234-0}}, language = {{eng}}, pages = {{1--6}}, title = {{Controlled island operation of part of the 50-kV grid in Southern Sweden}}, url = {{http://dx.doi.org/10.1109/PTC.2009.5282130}}, doi = {{10.1109/PTC.2009.5282130}}, year = {{2009}}, }