A new Approach to fast Distance Protection with Adaptive Features

Lindahl, Sture LU ; Saha, M. and Wikström, G. (1997) 6th International Conference on Developments in Power System Protection (Conf. Publ. No. 434)
Abstract
Distance relays are one of the most important components of protection available to power system protection engineers. Distance relays can benefit from ideas in the newly developed field of adaptive protection, and can offer an even more selective and sensitive form of protection, under a variety of power system configurations. A new fast adaptive distance protection scheme for single line to ground faults and multi-phase faults for EHV transmission lines is described in this paper. This scheme also performs well on series compensated lines. The new complementary fast tripping algorithms together with the earlier experienced algorithm and multiprocessor-based distance algorithm, have led to the development to an adaptive hybrid scheme.... (More)
Distance relays are one of the most important components of protection available to power system protection engineers. Distance relays can benefit from ideas in the newly developed field of adaptive protection, and can offer an even more selective and sensitive form of protection, under a variety of power system configurations. A new fast adaptive distance protection scheme for single line to ground faults and multi-phase faults for EHV transmission lines is described in this paper. This scheme also performs well on series compensated lines. The new complementary fast tripping algorithms together with the earlier experienced algorithm and multiprocessor-based distance algorithm, have led to the development to an adaptive hybrid scheme. This scheme is implemented into a well-proven hardware platform with moderate requirements on the communication. The protection scheme provides high speed tripping (less than one cycle) and high speed signalling. (Less)
Please use this url to cite or link to this publication:
author
; and
organization
publishing date
type
Chapter in Book/Report/Conference proceeding
publication status
published
subject
keywords
power system control, power transmission lines, power system protection, multiprocessing systems, adaptive control, power system relaying, relay protection
host publication
[Host publication title missing]
conference name
6th International Conference on Developments in Power System Protection (Conf. Publ. No. 434)
conference location
Nottingham, United Kingdom
conference dates
1997-03-25 - 1997-03-27
external identifiers
  • scopus:0030673069
ISBN
0 85296 672 5
DOI
10.1049/cp:19970022
language
English
LU publication?
yes
id
c56d2ff6-5385-4380-a85b-04b13e3251c6 (old id 4780604)
alternative location
http://digital-library.theiet.org/content/conferences/10.1049/cp_19970022
date added to LUP
2016-04-04 13:28:32
date last changed
2022-01-30 00:19:05
@inproceedings{c56d2ff6-5385-4380-a85b-04b13e3251c6,
  abstract     = {{Distance relays are one of the most important components of protection available to power system protection engineers. Distance relays can benefit from ideas in the newly developed field of adaptive protection, and can offer an even more selective and sensitive form of protection, under a variety of power system configurations. A new fast adaptive distance protection scheme for single line to ground faults and multi-phase faults for EHV transmission lines is described in this paper. This scheme also performs well on series compensated lines. The new complementary fast tripping algorithms together with the earlier experienced algorithm and multiprocessor-based distance algorithm, have led to the development to an adaptive hybrid scheme. This scheme is implemented into a well-proven hardware platform with moderate requirements on the communication. The protection scheme provides high speed tripping (less than one cycle) and high speed signalling.}},
  author       = {{Lindahl, Sture and Saha, M. and Wikström, G.}},
  booktitle    = {{[Host publication title missing]}},
  isbn         = {{0 85296 672 5}},
  keywords     = {{power system control; power transmission lines; power system protection; multiprocessing systems; adaptive control; power system relaying; relay protection}},
  language     = {{eng}},
  title        = {{A new Approach to fast Distance Protection with Adaptive Features}},
  url          = {{http://dx.doi.org/10.1049/cp:19970022}},
  doi          = {{10.1049/cp:19970022}},
  year         = {{1997}},
}