Anti-windup in mid-ranging control
(2005) 44th IEEE Conference on Decision and Control, and the European Control Conference, CDC-ECC '05 p.7570-7575- Abstract
- The implementation of anti-windup methods in mid-rangingcontrol needs further attention. It is demonstrated how use of standard anti-windup schemes may give unnecessary performance degradation during saturation. The problem isillustrated for two separate systems, control of oxygen concentration in a bio-reactor and temperature controlof a cooling system. In the paper, guidelines are derived for how to design the standard anti-windup scheme to recover performance. As an alternative a modified anti-windup scheme for mid-ranging control is presented that minimizes the performance degradation during saturation.
Please use this url to cite or link to this publication:
https://lup.lub.lu.se/record/535801
- author
- Haugwitz, Staffan LU ; Henningsson, Maria LU ; Velut, Stéphane LU and Hagander, Per LU
- organization
- publishing date
- 2005
- type
- Chapter in Book/Report/Conference proceeding
- publication status
- published
- subject
- keywords
- bio-reactor, process control, saturation, mid-ranging control, valve position control, anti-windup
- host publication
- Proceedings of the 44th IEEE Conference on Decision and Control and the 2005 European Control Conference
- pages
- 7570 - 7575
- publisher
- IEEE - Institute of Electrical and Electronics Engineers Inc.
- conference name
- 44th IEEE Conference on Decision and Control, and the European Control Conference, CDC-ECC '05
- conference location
- Seville, Spain
- conference dates
- 2005-12-12 - 2005-12-15
- external identifiers
-
- wos:000240653707037
- scopus:33847215516
- ISBN
- 0-7803-9568-9
- DOI
- 10.1109/CDC.2005.1583383
- language
- English
- LU publication?
- yes
- id
- 6d94b853-1443-4f6e-9f1c-a8c5fed84f7d (old id 535801)
- alternative location
- http://ieeexplore.ieee.org/iel5/10559/33412/01583383.pdf?tp=&arnumber=1583383&isnumber=33412
- date added to LUP
- 2016-04-04 12:08:32
- date last changed
- 2022-01-29 22:58:05
@inproceedings{6d94b853-1443-4f6e-9f1c-a8c5fed84f7d, abstract = {{The implementation of anti-windup methods in mid-rangingcontrol needs further attention. It is demonstrated how use of standard anti-windup schemes may give unnecessary performance degradation during saturation. The problem isillustrated for two separate systems, control of oxygen concentration in a bio-reactor and temperature controlof a cooling system. In the paper, guidelines are derived for how to design the standard anti-windup scheme to recover performance. As an alternative a modified anti-windup scheme for mid-ranging control is presented that minimizes the performance degradation during saturation.}}, author = {{Haugwitz, Staffan and Henningsson, Maria and Velut, Stéphane and Hagander, Per}}, booktitle = {{Proceedings of the 44th IEEE Conference on Decision and Control and the 2005 European Control Conference}}, isbn = {{0-7803-9568-9}}, keywords = {{bio-reactor; process control; saturation; mid-ranging control; valve position control; anti-windup}}, language = {{eng}}, pages = {{7570--7575}}, publisher = {{IEEE - Institute of Electrical and Electronics Engineers Inc.}}, title = {{Anti-windup in mid-ranging control}}, url = {{https://lup.lub.lu.se/search/files/5936979/625585.pdf}}, doi = {{10.1109/CDC.2005.1583383}}, year = {{2005}}, }