Evaluation of set points for moisture supply and volatile organic compounds as controlling parameters for demand controlled ventilation in multifamily houses

Abdul Hamid, Akram LU orcid ; el-Zoubi, S. and Omid, S. (2014) 13th International Conference on Indoor Air Quality and Climate, Indoor Air 2014
Abstract
The main purpose has been to evaluate existing set points (thresholds) and suggest proper set points, for the regulation of the air change rate in a demand controlled mechanical ventilation (DCV) system. The DCV is controlled by measurements in the supply and exhaust air of the vapor content and volatile organic compounds (VOCs) for each dwelling in multifamily houses. Results have been achieved through a literature review and laboratory tests. The threshold for the maximum ventilation rate (0.8 ac/h) should be set at 1000 ppm (CO2-eq.). Preferably, a minimum ventilation rate of 0.5 ac/h should be set with current thresholds (800-1000 ppm CO2-eq.). With a lower minimum ventilation rate (e.g. 0.1 ac/h) the lower threshold should be set at... (More)
The main purpose has been to evaluate existing set points (thresholds) and suggest proper set points, for the regulation of the air change rate in a demand controlled mechanical ventilation (DCV) system. The DCV is controlled by measurements in the supply and exhaust air of the vapor content and volatile organic compounds (VOCs) for each dwelling in multifamily houses. Results have been achieved through a literature review and laboratory tests. The threshold for the maximum ventilation rate (0.8 ac/h) should be set at 1000 ppm (CO2-eq.). Preferably, a minimum ventilation rate of 0.5 ac/h should be set with current thresholds (800-1000 ppm CO2-eq.). With a lower minimum ventilation rate (e.g. 0.1 ac/h) the lower threshold should be set at 450 ppm (CO2-eq). In order to deal with heavy moisture production the threshold for the moisture supply is suggested to be set at 3 g/m3. (Less)
Abstract (Swedish)
The main purpose has been to evaluate existing set points (thresholds) and suggest proper set points, for the regulation of the air change rate in a demand controlled mechanical ventilation (DCV) system. The DCV is controlled by measurements in the supply and exhaust air of the vapor content and volatile organic compounds (VOCs) for each dwelling in multifamily houses. Results have been achieved through a literature review and laboratory tests. The threshold for the maximum ventilation rate (0.8 ac/h) should be set at 1000 ppm (CO2-eq.). Preferably, a minimum ventilation rate of 0.5 ac/h should be set with current thresholds (800-1000 ppm CO2-eq.). With a lower minimum ventilation rate (e.g. 0.1 ac/h) the lower threshold should be set at... (More)
The main purpose has been to evaluate existing set points (thresholds) and suggest proper set points, for the regulation of the air change rate in a demand controlled mechanical ventilation (DCV) system. The DCV is controlled by measurements in the supply and exhaust air of the vapor content and volatile organic compounds (VOCs) for each dwelling in multifamily houses. Results have been achieved through a literature review and laboratory tests. The threshold for the maximum ventilation rate (0.8 ac/h) should be set at 1000 ppm (CO2-eq.). Preferably, a minimum ventilation rate of 0.5 ac/h should be set with current thresholds (800-1000 ppm CO2-eq.). With a lower minimum ventilation rate (e.g. 0.1 ac/h) the lower threshold should be set at 450 ppm (CO2-eq). In order to deal with heavy moisture production the threshold for the moisture supply is suggested to be set at 3 g/m3. (Less)
Please use this url to cite or link to this publication:
author
; and
organization
publishing date
type
Contribution to conference
publication status
published
subject
keywords
Demand, ventilation, multifamily, VOC, moisture
pages
8 pages
conference name
13th International Conference on Indoor Air Quality and Climate, Indoor Air 2014
conference location
Hong Kong, Hong Kong
conference dates
2014-07-07 - 2014-07-12
external identifiers
  • scopus:84924668216
language
English
LU publication?
yes
id
876adf5d-efbf-4345-aa8e-4410c5a76e1e
alternative location
http://www.isiaq.org/docs/paper/HP0901.pdf
date added to LUP
2017-10-17 10:42:49
date last changed
2024-01-14 10:34:30
@misc{876adf5d-efbf-4345-aa8e-4410c5a76e1e,
  abstract     = {{The main purpose has been to evaluate existing set points (thresholds) and suggest proper set points, for the regulation of the air change rate in a demand controlled mechanical ventilation (DCV) system. The DCV is controlled by measurements in the supply and exhaust air of the vapor content and volatile organic compounds (VOCs) for each dwelling in multifamily houses. Results have been achieved through a literature review and laboratory tests. The threshold for the maximum ventilation rate (0.8 ac/h) should be set at 1000 ppm (CO2-eq.). Preferably, a minimum ventilation rate of 0.5 ac/h should be set with current thresholds (800-1000 ppm CO2-eq.). With a lower minimum ventilation rate (e.g. 0.1 ac/h) the lower threshold should be set at 450 ppm (CO2-eq). In order to deal with heavy moisture production the threshold for the moisture supply is suggested to be set at 3 g/m3.}},
  author       = {{Abdul Hamid, Akram and el-Zoubi, S. and Omid, S.}},
  keywords     = {{Demand; ventilation; multifamily; VOC; moisture}},
  language     = {{eng}},
  title        = {{Evaluation of set points for moisture supply and volatile organic compounds as controlling parameters for demand controlled ventilation in multifamily houses}},
  url          = {{http://www.isiaq.org/docs/paper/HP0901.pdf}},
  year         = {{2014}},
}