On-off Control of an Active Load for Power System Damping - Theory and Field Test

Samuelsson, Olof LU and Akke, Magnus LU (1999) IEEE Power Engineering Society 1999 Winter Meeting 14(2). p.608-613
Abstract
Controlled resistive loads can contribute to damping of electro-mechanical oscillations. This paper presents an on-off damping controller for a single machine system. It was used at a field test in Southern Sweden to damp oscillations of a 0.9 MW hydro power generator. The controller used estimated machine frequency as input and controlled a 20 kW resistive load via thyristor switches. The field measurements are compared to time simulations and a systematic procedure for tuning the controller is given. The results indicate that on-off control of active loads is effective in terms of added damping and that it is simple to tune and implement
Please use this url to cite or link to this publication:
author
and
organization
publishing date
type
Chapter in Book/Report/Conference proceeding
publication status
published
subject
keywords
control system analysis control system synthesis damping hydroelectric generators hydroelectric power on-off control oscillations power system control
host publication
IEEE Transactions on Power Systems
volume
14
issue
2
pages
608 - 613
conference name
IEEE Power Engineering Society 1999 Winter Meeting
conference location
Piscataway, New York, United States
conference dates
1999-01-31
external identifiers
  • scopus:0032638896
ISSN
0885-8950
DOI
10.1109/59.761887
language
English
LU publication?
yes
id
62fcd348-fe74-44b3-9053-29874511f5ba (old id 4357686)
date added to LUP
2016-04-04 09:26:06
date last changed
2022-01-29 17:49:21
@inproceedings{62fcd348-fe74-44b3-9053-29874511f5ba,
  abstract     = {{Controlled resistive loads can contribute to damping of electro-mechanical oscillations. This paper presents an on-off damping controller for a single machine system. It was used at a field test in Southern Sweden to damp oscillations of a 0.9 MW hydro power generator. The controller used estimated machine frequency as input and controlled a 20 kW resistive load via thyristor switches. The field measurements are compared to time simulations and a systematic procedure for tuning the controller is given. The results indicate that on-off control of active loads is effective in terms of added damping and that it is simple to tune and implement}},
  author       = {{Samuelsson, Olof and Akke, Magnus}},
  booktitle    = {{IEEE Transactions on Power Systems}},
  issn         = {{0885-8950}},
  keywords     = {{control system analysis control system synthesis damping hydroelectric generators hydroelectric power on-off control oscillations power system control}},
  language     = {{eng}},
  number       = {{2}},
  pages        = {{608--613}},
  title        = {{On-off Control of an Active Load for Power System Damping - Theory and Field Test}},
  url          = {{http://dx.doi.org/10.1109/59.761887}},
  doi          = {{10.1109/59.761887}},
  volume       = {{14}},
  year         = {{1999}},
}