Estimation of the Zero Sequence Voltage on the D-side of a Dy Transformer by Using One Voltage Transformer on the D-side
(2008) 9th International Conference on Developments in Power System Protection (DPSP2008) p.517-522- Abstract
- The usual practice to measure the zero sequence voltage on the D-side of a transformer is to use three voltage transformers (VT), each of them connected between each phase and earth on the primary side and broken-delta connected on the secondary side. In this paper a method is presented for the estimation of the zero sequence voltage on the D-side of a Dy transformer by the use of only one VT connected between one phase and earth on the D-side and three VTs and current transformers (CT) on the y-side. The method is first introduced theoretically. Results from simulations and laboratory tests are then presented. The method proved to be accurate with an observed maximum error around 7% of nominal phase-to-earth voltage during transformer... (More)
- The usual practice to measure the zero sequence voltage on the D-side of a transformer is to use three voltage transformers (VT), each of them connected between each phase and earth on the primary side and broken-delta connected on the secondary side. In this paper a method is presented for the estimation of the zero sequence voltage on the D-side of a Dy transformer by the use of only one VT connected between one phase and earth on the D-side and three VTs and current transformers (CT) on the y-side. The method is first introduced theoretically. Results from simulations and laboratory tests are then presented. The method proved to be accurate with an observed maximum error around 7% of nominal phase-to-earth voltage during transformer energization and below 1% in all other cases. (Less)
Please use this url to cite or link to this publication:
https://lup.lub.lu.se/record/4357706
- author
- Sulla, Francesco LU and Samuelsson, Olof LU
- organization
- publishing date
- 2008
- type
- Chapter in Book/Report/Conference proceeding
- publication status
- published
- subject
- keywords
- current transformers nominal phase-to-earth voltage transformer energization voltage transformer zero sequence voltage zero sequence voltage estimation
- host publication
- The Institution of Engineering and Technology 9th international conference on developments in power systems protection : DPSP 2008, 17-20 March 2008.
- pages
- 517 - 522
- conference name
- 9th International Conference on Developments in Power System Protection (DPSP2008)
- conference location
- Glasgow, United Kingdom
- conference dates
- 2008-03-17
- external identifiers
-
- scopus:67449097413
- ISBN
- 978-0-86341-902-7
- language
- English
- LU publication?
- yes
- id
- e1aa4566-c9bd-4338-8b63-6a7894b07447 (old id 4357706)
- alternative location
- http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=4497039
- http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=4497039&tag=1
- date added to LUP
- 2016-04-04 14:22:26
- date last changed
- 2022-01-30 01:55:37
@inproceedings{e1aa4566-c9bd-4338-8b63-6a7894b07447, abstract = {{The usual practice to measure the zero sequence voltage on the D-side of a transformer is to use three voltage transformers (VT), each of them connected between each phase and earth on the primary side and broken-delta connected on the secondary side. In this paper a method is presented for the estimation of the zero sequence voltage on the D-side of a Dy transformer by the use of only one VT connected between one phase and earth on the D-side and three VTs and current transformers (CT) on the y-side. The method is first introduced theoretically. Results from simulations and laboratory tests are then presented. The method proved to be accurate with an observed maximum error around 7% of nominal phase-to-earth voltage during transformer energization and below 1% in all other cases.}}, author = {{Sulla, Francesco and Samuelsson, Olof}}, booktitle = {{The Institution of Engineering and Technology 9th international conference on developments in power systems protection : DPSP 2008, 17-20 March 2008.}}, isbn = {{978-0-86341-902-7}}, keywords = {{current transformers nominal phase-to-earth voltage transformer energization voltage transformer zero sequence voltage zero sequence voltage estimation}}, language = {{eng}}, pages = {{517--522}}, title = {{Estimation of the Zero Sequence Voltage on the D-side of a Dy Transformer by Using One Voltage Transformer on the D-side}}, url = {{http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=4497039}}, year = {{2008}}, }