Decentralized ventilation unit for window frame integration

Davidsson, H. LU ; Johansson, D. LU and Chowdary, S. K. (2022) SBE 2022 Delft Conference on Innovations for the Urban Energy Transition: Preparing for the European Renovation Wave In IOP Conference Series: Earth and Environmental Science 1085. p.32-32
Abstract

Swedish National Board of Housing, Building and Planning reported in "Energi i bebyggelsen"that 80 % of the detached houses in Sweden were under-ventilated, and had a flow of 0.23 l/(s·m2) on average instead of, by the code, required 0,35 l/(s·m2). Well known concerns here are lacking indoor environmental quality and a risk of moisture problems in certain rooms and in the envelope. The naturally ventilated houses have a higher airflow at low outdoor temperatures which increases the energy use for heating. Adding proper ventilation to all Swedish detached houses could according to Besmå's pre-study "Potential för energieffektivisering i småhus (2019)"increase the annual energy need by 5.5 TWh. Many of these use electric heating resulting... (More)

Swedish National Board of Housing, Building and Planning reported in "Energi i bebyggelsen"that 80 % of the detached houses in Sweden were under-ventilated, and had a flow of 0.23 l/(s·m2) on average instead of, by the code, required 0,35 l/(s·m2). Well known concerns here are lacking indoor environmental quality and a risk of moisture problems in certain rooms and in the envelope. The naturally ventilated houses have a higher airflow at low outdoor temperatures which increases the energy use for heating. Adding proper ventilation to all Swedish detached houses could according to Besmå's pre-study "Potential för energieffektivisering i småhus (2019)"increase the annual energy need by 5.5 TWh. Many of these use electric heating resulting in a heavy pressure on the electricity production and distribution. One way to solve this problem is to install mechanical ventilation with heat recovery. Installing such system in older houses is however often costly and often carries technical and practical problems. Ducts must be installed in every room in the building, requiring space which often leads to reconstruction of walls and ceilings. Another way to solve this is reinforce the existing ventilation in the house with a decentralised ventilation unit with heat recovery. The technical solution is to mount several smaller ventilation unit with heat recovery in the building skin in order to ventilate individual rooms. The solution does not require any ducts to be installed. This simplifies the installation and reduces the maintenance. In this report we study a decentralised ventilation unit with heat recovery intended to be installed in window frame to lower the cost of the combination of ventilation and window renovation. In this report we measure draft, short-circuiting between inlet and outlet air, air mixing in the room, noise and heat recovery efficiency of the ventilation unit. The results show that no draft and no short-circuit occurs and that the mixing of the air in the room is high and an efficiency of the heat recovery of approximately 70 %.

(Less)
Please use this url to cite or link to this publication:
author
; and
organization
publishing date
type
Chapter in Book/Report/Conference proceeding
publication status
published
subject
host publication
IOP Conference Series: Earth and Environmental Science
series title
IOP Conference Series: Earth and Environmental Science
volume
1085
edition
1
pages
32 - 32
conference name
SBE 2022 Delft Conference on Innovations for the Urban Energy Transition: Preparing for the European Renovation Wave
conference location
Delft, Netherlands
conference dates
2022-11-11 - 2022-11-13
external identifiers
  • scopus:85140063290
ISSN
1755-1307
DOI
10.1088/1755-1315/1085/1/012030
language
English
LU publication?
yes
id
90c5167f-fa21-409c-ae3c-804260c5f776
date added to LUP
2022-12-19 15:00:37
date last changed
2023-11-07 00:42:29
@inproceedings{90c5167f-fa21-409c-ae3c-804260c5f776,
  abstract     = {{<p>Swedish National Board of Housing, Building and Planning reported in "Energi i bebyggelsen"that 80 % of the detached houses in Sweden were under-ventilated, and had a flow of 0.23 l/(s·m2) on average instead of, by the code, required 0,35 l/(s·m2). Well known concerns here are lacking indoor environmental quality and a risk of moisture problems in certain rooms and in the envelope. The naturally ventilated houses have a higher airflow at low outdoor temperatures which increases the energy use for heating. Adding proper ventilation to all Swedish detached houses could according to Besmå's pre-study "Potential för energieffektivisering i småhus (2019)"increase the annual energy need by 5.5 TWh. Many of these use electric heating resulting in a heavy pressure on the electricity production and distribution. One way to solve this problem is to install mechanical ventilation with heat recovery. Installing such system in older houses is however often costly and often carries technical and practical problems. Ducts must be installed in every room in the building, requiring space which often leads to reconstruction of walls and ceilings. Another way to solve this is reinforce the existing ventilation in the house with a decentralised ventilation unit with heat recovery. The technical solution is to mount several smaller ventilation unit with heat recovery in the building skin in order to ventilate individual rooms. The solution does not require any ducts to be installed. This simplifies the installation and reduces the maintenance. In this report we study a decentralised ventilation unit with heat recovery intended to be installed in window frame to lower the cost of the combination of ventilation and window renovation. In this report we measure draft, short-circuiting between inlet and outlet air, air mixing in the room, noise and heat recovery efficiency of the ventilation unit. The results show that no draft and no short-circuit occurs and that the mixing of the air in the room is high and an efficiency of the heat recovery of approximately 70 %.</p>}},
  author       = {{Davidsson, H. and Johansson, D. and Chowdary, S. K.}},
  booktitle    = {{IOP Conference Series: Earth and Environmental Science}},
  issn         = {{1755-1307}},
  language     = {{eng}},
  pages        = {{32--32}},
  series       = {{IOP Conference Series: Earth and Environmental Science}},
  title        = {{Decentralized ventilation unit for window frame integration}},
  url          = {{http://dx.doi.org/10.1088/1755-1315/1085/1/012030}},
  doi          = {{10.1088/1755-1315/1085/1/012030}},
  volume       = {{1085}},
  year         = {{2022}},
}