Electricity Meters for Coordinated Voltage Control in Medium Voltage Networks with Wind Power

Leisse, Ingmar LU ; Samuelsson, Olof LU and Svensson, Jörgen LU (2010) Innovative Smart Grid Technologies Conference Europe (ISGT Europe), 2010 IEEE PES p.1-7
Abstract
During the last years the amount of electricity generated by Distributed Energy Resources (DER), especially wind turbines, has been increasing a lot. These Distributed Generation (DG) units are often connected to rural distribution networks, where they have a large impact on the voltage and the network losses. The network voltage at the customers point of connection is an important quality criteria and has to follow different standards as e.g. EN 50160. Therefore the voltage change caused by the integration of production units in the distribution network is an important aspect when integrating more DG in distribution networks and often a limiting factor for the maximum DG capacity which is possible to integrate into an existing network... (More)
During the last years the amount of electricity generated by Distributed Energy Resources (DER), especially wind turbines, has been increasing a lot. These Distributed Generation (DG) units are often connected to rural distribution networks, where they have a large impact on the voltage and the network losses. The network voltage at the customers point of connection is an important quality criteria and has to follow different standards as e.g. EN 50160. Therefore the voltage change caused by the integration of production units in the distribution network is an important aspect when integrating more DG in distribution networks and often a limiting factor for the maximum DG capacity which is possible to integrate into an existing network without reinforcement. Using the available voltage band more efficient by applying coordinated voltage control is a possibility to increase the hosted DG capacity in an existing distribution network without reinforcement of the network. To get the actual network status the new generation of electricity meters, which have the feasibility to communicate real time voltage measurements from the customers side to a network controller, give some benefits to a more flexible and coordinated voltage control in the network. The voltage range in the network will be used adapted to the actual load and generation situation instead of using worst case assumptions as it is good practice until now. A main part of the voltage control in medium voltage distribution networks is done by the on-load tap changer (OLTC) which takes the voltage at the consumers point of connection into account. A generic 10 kV distribution network with three typical types of feeders, as pure load, pure generation and mixed load and generation feeder, has been outlined. Coordinated voltage control is implemented by a central voltage controller. Simulations on the voltage and the network losses have been done and will be presented in this paper. The maximum DG capacity in the test system increases most when introducing coordinated control of the OLTC but also the use of reactive power adds some benefit. Further increase of the DG capacity by more extensive use of curtailment is always possible but due to economical aspects not favoured. (Less)
Please use this url to cite or link to this publication:
author
; and
organization
publishing date
type
Chapter in Book/Report/Conference proceeding
publication status
published
subject
keywords
coordinated voltage control, distributed generation (DG), distribution network, electricity meters
host publication
Innovative Smart Grid Technologies Conference Europe (ISGT Europe), 2010 IEEE PES
pages
1 - 7
conference name
Innovative Smart Grid Technologies Conference Europe (ISGT Europe), 2010 IEEE PES
conference location
Gothenburg, Sweden
conference dates
2010-10-11 - 2010-10-13
external identifiers
  • scopus:78650526612
ISBN
978-1-4244-8508-6
978-1-4244-8509-3
DOI
10.1109/ISGTEUROPE.2010.5638977
language
English
LU publication?
yes
id
c86af055-e157-4679-b5a4-d8d70b370538 (old id 1790315)
alternative location
http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=5638977
date added to LUP
2016-04-04 13:03:53
date last changed
2022-01-29 23:41:20
@inproceedings{c86af055-e157-4679-b5a4-d8d70b370538,
  abstract     = {{During the last years the amount of electricity generated by Distributed Energy Resources (DER), especially wind turbines, has been increasing a lot. These Distributed Generation (DG) units are often connected to rural distribution networks, where they have a large impact on the voltage and the network losses. The network voltage at the customers point of connection is an important quality criteria and has to follow different standards as e.g. EN 50160. Therefore the voltage change caused by the integration of production units in the distribution network is an important aspect when integrating more DG in distribution networks and often a limiting factor for the maximum DG capacity which is possible to integrate into an existing network without reinforcement. Using the available voltage band more efficient by applying coordinated voltage control is a possibility to increase the hosted DG capacity in an existing distribution network without reinforcement of the network. To get the actual network status the new generation of electricity meters, which have the feasibility to communicate real time voltage measurements from the customers side to a network controller, give some benefits to a more flexible and coordinated voltage control in the network. The voltage range in the network will be used adapted to the actual load and generation situation instead of using worst case assumptions as it is good practice until now. A main part of the voltage control in medium voltage distribution networks is done by the on-load tap changer (OLTC) which takes the voltage at the consumers point of connection into account. A generic 10 kV distribution network with three typical types of feeders, as pure load, pure generation and mixed load and generation feeder, has been outlined. Coordinated voltage control is implemented by a central voltage controller. Simulations on the voltage and the network losses have been done and will be presented in this paper. The maximum DG capacity in the test system increases most when introducing coordinated control of the OLTC but also the use of reactive power adds some benefit. Further increase of the DG capacity by more extensive use of curtailment is always possible but due to economical aspects not favoured.}},
  author       = {{Leisse, Ingmar and Samuelsson, Olof and Svensson, Jörgen}},
  booktitle    = {{Innovative Smart Grid Technologies Conference Europe (ISGT Europe), 2010 IEEE PES}},
  isbn         = {{978-1-4244-8508-6}},
  keywords     = {{coordinated voltage control; distributed generation (DG); distribution network; electricity meters}},
  language     = {{eng}},
  pages        = {{1--7}},
  title        = {{Electricity Meters for Coordinated Voltage Control in Medium Voltage Networks with Wind Power}},
  url          = {{http://dx.doi.org/10.1109/ISGTEUROPE.2010.5638977}},
  doi          = {{10.1109/ISGTEUROPE.2010.5638977}},
  year         = {{2010}},
}